The IS-A105N+IS-L101L unit is an intrinsically safe field mounting combined alarm horn with L.E.D. beacon/light which provides a a loud audible and bright flashing visual signal utilising a common zener barrier or galvanic isolator. The alarm horn features an alarm accept function - by closing a pair of external contacts (i.e push switch) the operator may silence the alarm for set periods between 5 seconds and 2 hours. If after the preset time the alarm condition still exists the sounder will activate again. Certified for use in application requiring Ex ia or Class I Div 1 equipment the IS-A105N+IS-L101L is a globally accepted solution to fire or process control signalling.
Specification
Sounder/horn: | |
Nominal output: | 105dB(A) @ 1m +/- 3dB - Tone 2* [96dB(A) @ 10ft/3m] |
No. of tones: | 49 (UKOOA/PFEER compliant) |
No. of stages: | 3 |
Volume control: | Max. 105dB(A); Min. 96dB(A) - Tone 2 |
Effective range: | 60m/197ft @ 1KHz |
Beacon/light: | |
Light source: | Array of 6 high intensity L.E.D’s |
L.E.D. colours: | Red, Amber, Blue & Green |
Standalone mode: | 2Hz (2 double flashes per second) |
Effective intensity cd: | 48cd* - measured ref. to I.E.S. |
Flash rate: | On: 1 Hz (1 double flash per second) Silenced: 2 Hz (2 double flashes per second) (alarm accepted) |
General: | |
Voltage: | 16-28vdc via Zener barrier or galvanic isolator |
Current: | 25mA typical when powered from 24v supply via 28v 300 Ohm Zener barrier |
Ingress protection: | IP66 |
Rating: | Continuous |
Housing material: | UL94V0 & 5VA FR ABS |
Housing colour: | RAL3000 Red |
Fixings: | Stainless Steel |
Cable entries: | 2 x M20 clearance gland knockouts. Custom configurations also available. |
Terminals: | 0.5 to 2.5mm² |
Operating temp: | -40° to +60°C [-40° to +140°F] |
Storage temp: | -40° to +70°C [-40° to +158°F] |
Relative humidity: | 90% at 20°C [68°F] |
Weight: | 1.15kg/2.53Ibs |
*SPL data +/-3dB(A). Measured at optimum voltage. |
Part Codes
IS-A105N-R | ||
IS-L101L-R/[x] | ||
ATEX / IECEx / FM | ||
II 1G Ex ia IIC T4 Ga (-40ºC <=Ta<= +60°C) | ||
IS Class I, Zone 0, AEx ia IIC T4 Ta = +60°C | ||
IS Class l, Division 1, Groups A, B, C, D T4 | ||
GOST-R | ||
0ExiaIICT4 IP65 -40° to +60°C | ||
[x] : LED colour R: Red, A: Amber, B: Blue, G: Green | ||
May be powered from any certified Zener barrier or , galvanic isolator whose output parameters do not exceed : |
||
Uo : 28VDC | Io : 93mA | Po : 1.2W |
Tone Table
Stage 1 | WAV file | Frequency Description. | Stg 2 | Stg 3 |
---|---|---|---|---|
T 1 | ↓ | 340 Hz Continuous | T 2 | T 5 |
T 2 | ↓ | 800/1000Hz @ 0.25 sec Alternating | T 17 | T 5 |
T 3 | ↓ | 500/1200Hz @ 0.3Hz 0.5 sec Slow Whoop | T 2 | T 5 |
T 4 | ↓ | 800/1000Hz @ 1Hz Sweeping | T 6 | T 5 |
T 5 | ↓ | 2400Hz Continuous | T 3 | T 20 |
T 6 | ↓ | 2400/2900Hz @ 7Hz Sweeping | T 7 | T 5 |
T 7 | ↓ | 2400/2900Hz @ 1Hz Sweeping | T 10 | T 5 |
T 8 | ↓ | 500/1200/500Hz @ 0.3Hz Sweeping | T 2 | T 5 |
T 9 | ↓ | 1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P. | T 15 | T 2 |
T 10 | ↓ | 2400/2900Hz @ 2Hz Alternating | T 7 | T 5 |
T 11 | ↓ | 1000Hz @ 1Hz Intermittent | T 2 | T 5 |
T 12 | ↓ | 800/1000Hz @ 0.875Hz Alternating | T 4 | T 5 |
T 13 | ↓ | 2400Hz @ 1Hz Intermittent | T 15 | T 5 |
T 14 | ↓ | 800Hz 0.25sec on, 1 sec off Intermittent | T 4 | T 5 |
T 15 | ↓ | 800Hz Continuous | T 2 | T 5 |
T 16 | ↓ | 660Hz 150mS on, 150mS off Intermittent | T 18 | T 5 |
T 17 | ↓ | 544Hz (100mS)/440Hz (400mS) - NF S 32-001 | T 2 | T 27 |
T 18 | ↓ | 660Hz 1.8sec on, 1.8sec off Intermittent | T 2 | T 5 |
T 19 | ↓ | 1.4KHz-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s -NFC48-265 | T 2 | T 5 |
T 20 | ↓ | 660Hz Continuous | T 2 | T 5 |
T 21 | ↓ | 554Hz/440Hz @ 1Hz Alternating | T 2 | T 5 |
T 22 | ↓ | 544Hz @ 0.875 sec. Intermittent | T 2 | T 5 |
T 23 | ↓ | 800Hz @ 2Hz Intermittent | T 6 | T 5 |
T 24 | ↓ | 800/1000Hz @ 50Hz Sweeping | T 29 | T 5 |
T 25 | ↓ | 2400/2900Hz @ 50Hz Sweeping | T 29 | T 5 |
T 26 | ↓ | Bell | T 2 | T 15 |
T 27 | ↓ | 554Hz Continuous | T 26 | T 5 |
T 28 | ↓ | 440Hz Continuous | T 2 | T 5 |
T 29 | ↓ | 800/1000Hz @ 7Hz Sweeping | T 7 | T 5 |
T 30 | ↓ | 300Hz Continuous | T 2 | T 5 |
T 31 | ↓ | 660/1200Hz @ 1Hz Sweeping | T 26 | T 5 |
T 32 | ↓ | Two T chime. | T 26 | T 15 |
T 33 | ↓ | 745Hz @ 1Hz Intermittent | T 2 | T 5 |
T 34 | ↓ | 1000 & 2000Hz @ 0.5 sec Alternating - Singapore | T 38 | T 45 |
T 35 | ↓ | 420Hz @ 0.625 sec Australian Alert | T 36 | T 5 |
T 36 | ↓ | 500-1200Hz 3.75sec /0.25sec. Australian Evac. | T 35 | T 5 |
T 37 | ↓ | 1000Hz Continuous - PFEER Toxic Gas | T 9 | T 45 |
T 38 | ↓ | 2000Hz Continuous | T 34 | T 45 |
T 39 | ↓ | 800Hz 0.25sec on, 1 sec off Intermittent | T 23 | T 17 |
T 40 | ↓ | 544Hz (100mS)/440Hz (400mS) - NF S 32-001 | T 31 | T 27 |
T 41 | ↓ | Motor Siren - slow rise to 1200 Hz | T 2 | T 5 |
T 42 | ↓ | Motor Siren - slow rise to 800 Hz | T 2 | T 5 |
T 43 | ↓ | 1200 Hz Continuous | T 2 | T 5 |
T 44 | ↓ | Motor Siren - slow rise to 2400 Hz | T 2 | T 5 |
T 45 | ↓ | 1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm | T 38 | T 34 |
T 46 | ↓ | 1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P. | T 47 | T 37 |
T 47 | ↓ | 1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm | T 46 | T 37 |
T 48 | ↓ | 420Hz @ 0.625 sec Australian Alert | T 49 | T 5 |
T 49 | ↓ | 500-1200Hz 3.75sec /0.25sec. Australian Evac. | T 26 | T 37 |